Post Banner
Pressure Switch with Delay

How Adjustable Hysteresis Improves Hydraulic Pressure Control

How Adjustable Hysteresis Improves Hydraulic Pressure Control

Why Unnecessary Pressure Switching Happens in Hydraulic Systems

Hydraulic systems rarely operate at perfectly constant pressure. During pump startup, valve switching, load changes and normal machine operation, pressure may fluctuate around the configured switching threshold.

These variations can cause problems when a pressure switch uses only a single switching point.

For example, if the pressure repeatedly moves above and below the setpoint, the relay may switch on and off frequently. This behavior is known as relay chattering.

Frequent switching can increase electrical contact wear, create unnecessary equipment starts and stops, and make alarm management more difficult.

One practical way to improve switching stability is to use an adjustable hysteresis pressure switch.

By defining separate switching and release pressures, engineers can establish a suitable operating band for the hydraulic system.

1. Understanding Pressure Fluctuations in Hydraulic Systems

Pressure variations are common in industrial hydraulic equipment.

Several operating conditions can contribute to these fluctuations:

Pump Startup

When a hydraulic pump starts, pressure may change as the system builds up to its operating condition. Cold hydraulic oil, system resistance and pump characteristics can influence the startup pressure response.

Valve Switching

Opening or closing a hydraulic valve changes the flow conditions inside the system. Depending on the system design, this can produce temporary pressure fluctuations.

Changes in Mechanical Load

When the load on a hydraulic cylinder or actuator changes, the required hydraulic pressure may also change.

Pressure Pulsation

Pump operation and other cyclic processes can create recurring pressure variations. These fluctuations may cause repeated switching if the pressure remains close to the configured threshold.

Understanding these conditions is important before adjusting pressure switch parameters.

2. What Is Hysteresis in a Pressure Switch?

Hysteresis is the difference between the pressure at which a relay switches and the pressure at which it returns to its previous state.

Instead of using one pressure value for both actions, a pressure switch with adjustable hysteresis uses two separate values.

For example, consider a high-pressure alarm:

  • Switching pressure: 100 bar
  • Release pressure: 95 bar

When pressure rises to 100 bar, the relay activates.

The relay remains active while pressure decreases from 100 bar to 95 bar. It resets only when pressure falls below the configured release value.

The 5 bar difference is the hysteresis.

<AsyncImage query=”industrial hydraulic pressure switch hysteresis switching pressure release pressure technical diagram graph” aspectRatio=”16:9″ width=”100%” fit=”contain”/>

This separation helps prevent repeated relay switching when pressure fluctuates slightly around the switching threshold.

Why Adjustable Hysteresis Matters

The appropriate hysteresis setting depends on the application.

If the difference is too small, normal pressure fluctuations may still cause frequent switching.

If the difference is too large, the system may allow pressure to move farther than desired before the relay resets.

Engineers should therefore select switching and release values according to the system’s normal pressure variation, operating limits and control requirements.

3. DR3602: Intelligent Pressure Control with Two Independent Relays

The FANDE DR3602 Intelligent Pressure Switch combines pressure measurement, local display and relay control in one instrument.

Its two independent relay outputs allow engineers to configure separate pressure control conditions.

For example:

  • Relay 1 can be configured for a high-pressure alarm.
  • Relay 2 can be configured for a low-pressure alarm.

Each relay has independently configurable switching and release values.

The 4-digit LED display provides local pressure indication and supports on-site parameter adjustment.

Key Features

  • Two independent relay outputs: Supports up to two pressure control points.
  • Adjustable hysteresis: Separate switching and release values for each relay.
  • 4-digit LED display: Provides clear local pressure readings.
  • Display filtering: Adjustable filter coefficient helps stabilize displayed readings.
  • 4–20 mA output: Two-wire analog signal for compatible monitoring and control systems.
  • Wide pressure range: Configurable from vacuum ranges to high-pressure ranges up to 1000 bar.
  • Industrial construction: Stainless steel 304 housing and stainless steel 316L diaphragm.
  • 24VDC power supply: Suitable for common industrial control systems.

These functions make the DR3602 suitable for hydraulic pressure monitoring, pump control and industrial automation applications.

4. How to Configure Two Pressure Control Points

The DR3602 allows users to configure two independent relay switching conditions.

For example, a hydraulic system may require both high-pressure and low-pressure monitoring.

High-Pressure Alarm

Suppose the system requires a high-pressure alarm at 100 bar, with a release pressure of 95 bar.

The settings are:

ParameterSetting
Relay 1 switching pressure100 bar
Relay 1 release pressure95 bar
Hysteresis5 bar

When pressure reaches 100 bar, Relay 1 activates. It resets when pressure falls to 95 bar.

Low-Pressure Alarm

A separate relay can be configured to monitor low pressure.

For example:

ParameterSetting
Relay 2 switching pressure40 bar
Relay 2 release pressure45 bar
Hysteresis5 bar

When pressure falls to 40 bar, Relay 2 activates. It resets when pressure rises to 45 bar.

These are illustrative settings only. Actual switching values and relay logic should be selected according to the hydraulic system’s operating requirements.

5. Hysteresis and Display Filtering: Understanding the Difference

Hysteresis and display filtering serve different purposes.

Hysteresis controls relay switching behavior.

It defines the difference between the relay’s switching pressure and release pressure. This helps prevent repeated relay changes caused by small pressure variations around the setpoint.

Display filtering stabilizes the displayed pressure reading.

The DR3602 includes a FILT parameter that adjusts the display filter coefficient. A higher filtering setting can make the displayed reading more stable, but it may also make the display respond more slowly to pressure changes.

Neither function should automatically be treated as a programmable response delay.

If an application requires the relay to ignore a pressure event for a defined period, engineers should confirm that the selected pressure controller supports a dedicated relay delay function or implement the required timing logic in the PLC.

This distinction is important for applications involving short-duration pressure spikes during startup.

6. Integrating DR3602 with Industrial Control Systems

The DR3602 combines pressure measurement and relay control in one device.

Its relay outputs can be connected to compatible alarm circuits, contactors or control inputs, depending on the electrical design.

The optional 4–20 mA output can transmit pressure readings to a PLC, DCS or other compatible monitoring equipment.

A typical system arrangement is:

Hydraulic Pressure → DR3602 → Relay Outputs + 4–20 mA Signal → Control System

This configuration allows operators to monitor pressure locally while using relay signals for independent pressure control conditions.

For applications requiring remote digital communication, confirm the available communication configuration before ordering.

7. DR3602 Technical Specifications

ParameterSpecification
Measurement range-1 bar to 1000 bar, depending on configuration
Pressure typeGauge, absolute or sealed gauge
Accuracy±0.1% FS / ±0.25% FS / ±0.5% FS
Long-term stability±0.3% FS (1 year)
OutputTwo relay outputs + 4–20 mA DC
Power supply24 VDC
Relay contact load24 VDC, 1.2 A
Compensated temperature0°C to +50°C
Working temperature-30°C to +70°C
HousingStainless steel 304
DiaphragmStainless steel 316L
Protection ratingIP44
Pressure connectionsNPT1/2, NPT1/4, G1/2, G1/4, M20×1.5

Specifications should be confirmed against the selected product configuration before ordering.

8. Applications of Adjustable Hysteresis Pressure Switches

Adjustable hysteresis is useful in industrial systems where pressure naturally fluctuates around a control threshold.

Typical applications include:

Hydraulic Power Units

Monitor high and low pressure conditions and configure separate relay responses for equipment protection.

Industrial Pump Systems

Use independent pressure thresholds for pump start, stop or alarm functions, according to the system control design.

Process Equipment

Monitor pressure changes in pipelines, machinery and industrial production equipment.

Automation and Equipment Protection

Provide local pressure indication and relay signals for integration with industrial control circuits.

Conclusion: Improve Pressure Control with the Right Switching Settings

Pressure fluctuations are a normal part of many hydraulic and industrial processes. However, if a pressure switch uses unsuitable switching and release values, these fluctuations can cause unnecessary relay operation.

An adjustable hysteresis pressure switch provides a practical way to establish a suitable switching band and improve control stability.

The FANDE DR3602 Intelligent Pressure Switch offers two independent relay outputs, adjustable switching and release values, a 4-digit LED display and an optional 4–20 mA output.

For hydraulic systems and industrial pressure control applications, these functions provide greater flexibility when configuring pressure alarms and control conditions.

Looking for an intelligent pressure switch for your hydraulic system?

Explore the FANDE DR3602 Intelligent Pressure Switch or contact our engineering team with your pressure range, switching points and control requirements.

🔧 Need a Reliable Pressure Switch with Delay?

Contact our engineering team for a free consultation on DR3602 solutions tailored to your application.

View DR3602 Product Details →

📧 [email protected]

Tags: #pressureswitchwithdelaytimer #adjustablehysteresis #NEMA4Xpressureswitch #DR3602